Technical Data  
Control switch complete device, 4-pole

Connection Terminals 2.5 mm2
Conductor terminals 4 x 2.5 mm2
Rated insulation voltage max. AC 690 V
Nominal current max. 16 A
Cable entry Standard version:
M 20 x 1.5 for cables with ø 6 to 12 mm

Special version:
M 20 x 1.5 for cables with ø 5 to 9 mm
M 25 x 1.5 for cables with ø 13 to 18 mm
M 25 x 1.5 for cables with ø 9 to 16 mm
Enclosure Thermoplastic
Protection class IP 66
Contact material AgSnO2
Switching function 4 switch contacts
NC/NO in different switch permutations
Latching and momentary-contact functions
with different switch positions
Contacts contacts with positive break operation
Switch isolator
DIN EN 60947-3 (main motor switch)
P/AC-3/AC-23 A AC-3 AC-23
230 V 3ph/3kW 1ph/2.2 kW
400 V 3ph/5.5 kW 1ph/3 kW
le = AC-23/400 V/10 A
Control switch
DIN EN 60947-5-1
(auxiliary circuit switch)
AC-15 400 V 10 A
AC-12 400 V 16 A
DC-13 24 V 1 A
Electrical data
Rated insulation voltage Ui = 690 V
Ue = 400 V
Rated impulse strength Uimp = 6 kV
Conditional rated short/circuit current
at 400 V
ie = 4 kA
Short circuit current
(general-purpose l.v.h.b.c. back-up fuse for
the protection of cables and circuits)

max. 16 A
Nominal thermal current
(+40 °C)
Ithe = 16 A
(+60 °C) Ithe = 11 A